探火管及释放管的安装应符合下列要求
(1)探火管连接部件应采用专用连接件。
(1) the fire pipe connection shall be used for special connection.
(2)探火管应按设计要求敷设,并应采用专用管夹固定,固定措施应保证探火管牢固、工作可靠;当被保护对象为电线电缆时,宜将探火管随电线电缆敷设,并应用专用的管夹固定。
(2) the fire pipe shall be laid out according to the design requirements, and shall be fixed with the special pipe clamps, and the fixed measures shall ensure that the fire pipes are strong and the work is reliable. When protected by a wire cable, the fire tube shall be laid with the cable cable, and the special pipe clamp shall be fixed.
(3)释放管的三通分流参数应均衡。
The three-way shunt parameter of the release tube should be balanced.
(4)探火管穿过墙壁或设备壳体时,应采用专用保护件或连接件,防止探火管磨损。
(4) when the fire tube passes through the wall or the casing of the device, special protective parts or fittings shall be adopted to prevent the pipe from being worn.
(5)探火管不应布置在温度大于80℃的物体表面。
(5) fire detecting tube should not be decorated on the surface of the object that temperature greater than 80 ℃.
(6)探火管压力表的安装位置应便于观察。
(6) the position of the fire tube pressure gauge shall be easy to observe.