返回首页

南阳空调诚信维修

本站导航

新闻动态

当前位置:网站首页 > 新闻动态 > 详细信息
变电站充氮灭火装置的运行与维护
添加时间:2017/4/19 14:31:11     浏览次数:
1、检查氮气瓶压力是否正常。从运行经验上看,氮气压力低是常见的事件,需要及时通知检修人员补充或更换氮气瓶。

1, check whether the nitrogen cylinder pressure is normal. From the point of view of operating experience, low nitrogen pressure is a common event, need to promptly notify the maintenance personnel to supplement or replace the nitrogen cylinder. 

2、检查管路、阀门(排油阀、检修阀、单向阀)有无渗漏。

2, check the piping, valves, oil discharge valve, valve, check valve repair) with and without leakage. 

3、非紧急情况下,严禁按下【“手动”和“手动确认”】、【“紧急启动”和“紧急启动确认”】按钮!

3, the case of an emergency, it is forbidden to press the "manual" and "manual validation" 】 【, the "emergency start" and "emergency start confirmation" 】 button! 

4、装置运行时,排油阀、氮气释放阀锁定铜销必须取下!否则无法电气启动装置,贻误火情!

4, the device runs, emptying valve, nitrogen release valve lock copper pin must be removed! Cannot electrical initiating device, otherwise bungle the fire! 

5、装置退出时,检修阀必须关上,排油阀、氮气释放阀锁定铜销插上,将控制柜和消防柜电源断开。

5, unit exits, repair valves must be closed, emptying valve, nitrogen release valve locking pin with brass, the control cabinet and fire control cabinet power disconnect. 

上一页  电气设备的防火措施   
下一页  消防给水设备产品
  • 关于我们
  • 新闻动态
  • 案例展示
  • 网上订单
  • 联系我们
  • 产品分类1
  • 产品分类2
  • 产品分类3

Copyright © 技术支持:遨游网络

  • 联系我们
  • 网上订单
  • 工程案例
  • 本站导航

搜索

  • 关于我们
  • 新闻动态
  • 案例展示
  • 网上订单
  • 联系我们
  • 产品分类1
  • 产品分类2
  • 产品分类3