1、探火管灭火装置安装前,应对容器阀、探火管、释放管、喷头等进行外观质量检查,并应符合下列规定:
1. Before the installation of the fire extinguishing device, the exterior quality of the container valve, the fire detector, the release pipe and the sprinkler head shall be inspected, and the following provisions shall be complied with:
(1)组件无碰撞变形及其它机械性损伤;
(1) collision free deformation and other mechanical damage of components.
(2)组件外露非机械加工表面保护涂层完好;
(2) the components are exposed and non machined, and the surface protective coating is intact.
(3)组件所有外露接口均设有防护堵、盖,且封闭良好,接口螺纹无损伤;
(3) all exposed interfaces of the components are equipped with protective plugs and covers, which are well sealed and have no damage to the interface threads.
(4)铭牌清晰,其内容应符合国家有关标识的规定。
(4) the nameplate is clear and its contents should conform to the relevant national identification requirements.
2、探火管灭火装置安装前应检查灭火剂储存容器内的充装量和充装压力,并应符合设计要求。
2. Before installing the fire extinguishing device, the filling quantity and pressure in the storage container of the fire extinguishing agent should be checked and the design requirements should be met.
3、灭火剂储存容器的安装应符合下列要求:
3. Installation of fire extinguishing storage containers should meet the following requirements:
(1)安装位置应符合设计要求;
(1) the installation location should meet the design requirements.
(2)安装已充装好的灭火剂储存容器之前,不应将探火管连接至灭火剂储存容器容器阀上;
(2) Fire detectors should not be connected to the container valve of the filled fire extinguishing agent storage container before installation.
(3)灭火剂储存容器应直立安装,固定储存容器支架、框架应牢固、可靠,且采取防腐处理措施;
(3) Fire extinguishing agent storage containers shall be erected, and the support and frame of the fixed storage containers shall be firm and reliable, and anti-corrosion measures shall be taken.
(4)灭火剂储存容器安全泄放装置的泄压方向不应朝向操作面,且不应对人身和设备造成危害;
(4) The pressure relief direction of the safety relief device of the fire extinguishing agent storage container should not be directed towards the operating surface, and should not cause harm to people and equipment.
(5)容器阀上设有压力表的,其安装位置应正确,示值灵敏、准确。
(5) the pressure gauge on the vessel valve should be installed correctly, and the indication value is sensitive and accurate.
4、探火管及释放管的安装应符合下列要求:
4. Installation of fire hose and release pipe should meet the following requirements:
(1)探火管连接部件应采用专用连接件。
(1) special connections should be used for connection parts of fire hose.
(2)探火管应按设计要求敷设,并应采用专用管夹固定,固定措施应保证探火管牢固、工作可靠;当被保护对象为电线电缆时,宜将探火管随电线电缆敷设,并应用专用的管夹固定。
(2) Fire detectors should be laid according to the design requirements, and should be fixed with special pipe clamps. Fixing measures should ensure that the fire detectors are firm and reliable. When the protected objects are wires and cables, fire detectors should be laid with wires and cables and fixed with special pipe clamps.
(3)释放管的三通分流参数应均衡。
(3) the three way shunting parameters of the release tube should be balanced.
(4)探火管穿过墙壁或设备壳体时,应采用专用保护件或连接件,防止探火管磨损。
(4) When a fire detector pipe passes through a wall or a shell of equipment, special protective parts or connectors shall be used to prevent the wear and tear of the fire detector tube.
(5)探火管不应布置在温度大于80℃的物体表面。
(5) the fire hose should not be placed on the surface of the object at a temperature greater than 80 degrees.
(6)探火管压力表的安装位置应便于观察。
(6) the installation position of the probe tube pressure gauge should be easy to observe.
(7)释放管的安装应符合现行国家标准GB50193、《气体灭火系统施工验收规范》GB50263和GB50347的规定。
(7) The installation of the release pipe shall conform to the current national standards GB50193, GB50263 and GB5034 7.
5、喷头的安装应符合现行国家标准GB50263和GB50347的规定。
5, the installation of sprinklers should comply with the existing national standards GB50263 and GB50347.